无源保护
局放
带电闭锁
故障指示器
带电指示器
负荷开关控制器
  • RP-400D
  • RP-DM500P03
  • Live locking device
  • Fault Indicator
  • Live Indicator
  • Three-position Isolation Controller
RP-400D

Conventional relay protection relies on external power and risks outage failure amid disasters and extreme weather. The RP-400 passive protection device takes power from CT secondary circuits, eliminating external power dependence and enabling maintenance-free feeder protection.

Main Function Features

CT Self-power Supply Low Pickup Current High Sampling Accuracy Multiple Power Supply Modes Maintenance-free Live Hot Plugging

Ratings & Specifications

  • Auxiliary Power Supply100-230VAC/DC,≤4W;
  • Minimum Pickup Current3-phase: 70mA; 2-phase: 100mA; 1-phase: 150mA;
  • AC Sampling CurrentRated 1A;
  • Measuring Range0.2~20A;
  • Trip Output24VDC-135mJ;
  • Operating Temperature-20~70℃;
  • Altitude<5000m;
  • Debug Power SupplyUSB 5V;

Outline dimension

Outline dimension
RP-DM500P03

The power distribution circuit state monitoring device is installed in each interval of the switch cabinet and is used for monitoring various parameters and States of the power distribution circuit. The device integrates a live display function, a partial discharge monitoring function, a cable head wireless thermometry function and a fault state indication function.

Main Function Features

Diverse Functions In-place Display Communication High Sensitivity Independent algorithm Easy Installation

Ratings & Specifications

  • Power supply modeDC 24V or DC 48V
  • Voltage level10kV/35kV
  • Communication interfaceRS-485
  • Communication protocolStandard Modbus-RTU
  • Baud rate4800/9600/115200bps
  • Debugging interfaceUSB
  • Sensor typeCapacitive coupling sensor, fault current sensor, wireless thermometry sensor
  • Installation modeRecessed panel mount

Overall dimension (unit: mm)

Overall dimension (unit: mm)
Live locking device

The device is suitable for parts needing locking, such as quarantine switches, grounding switches and the like of various switch cabinets to realize locking and prevent misoperation, and is an indispensable locking device in a power grid system.

Main Function Features

Standardization Locking mechanism Safe and reliable Over-temperature protection Aesthetic design Easy operation

Ratings & Specifications

  • Operating voltageDC24V、DC48V、DC125V、AC/DC120V、AC/DC220V
  • Standby power consumption < 0.4W
  • Ambient temperature-40℃~+70℃
  • Ambient humidity≤ 95% RH, no condensation
  • Insulation resistance≥10MΩ
  • Insulation strengthAC2000V 50Hz/1min
  • Impulse voltage1.2/50μs 5000V
  • Weight≤ 260g

Opening size (unit: mm)

Opening size (unit: mm)
Fault Indicator

A new type of detection equipment that monitors each circuit in real time. When a line fault occurs, it can alert or directly indicate the faulty cable, which is of great significance for improving work efficiency and quickly restoring power supply.

Main Function Features

Short-Circuit Alarm Ground Fault Alarm Auto Reset Manual Reset Test

Ratings & Specifications

  • Applicable Voltage Class6~0.5KV
  • Rated Load0-600A
  • Operating Power SupplyHigh Capacity 3.6V ER14505 Lithium Battery
  • Response Time0.06S≤T≤3S
  • Static Power Consumption≤10uW
  • Operating Ambient Temperature-40°C≤T≤+75°C
  • Ground Fault Pickup Value20A
  • Short-Circuit Fault Pickup Value800A

Outline dimension

Outline dimension
Live Indicator

This product offers real-time switchgear circuit voltage feedback for maintenance staff. With built-in low-power LEDs, it features low consumption, stable performance and high reliability. Suitable for 3.6~40.5kV indoor high-voltage equipment, it monitors live circuits and boosts equipment anti-misoperation ability with switches.

Main Function Features

Circuit Voltage Condition Monitoring Low Power & Stable Performance Adaptable to High-Voltage Environments Linked Anti-misoperation Interlock

Ratings & Specifications

  • Working Power SupplyAC/DC110V/220V or DC48V或DC24V(Please specify when ordering)
  • Applicable Voltage Class3.6KV~40.5KV
  • Pickup Voltage15%~40%Un
  • Contact Rating5A/250V AC or 5A/30V DC
  • Power Consumption≤5W
  • Ambient Temperature-25°C~+60°C
  • Relative Humidity (RH)Daily average≤95%,monthly average≤90%

Outline dimension

Outline dimension
Three-position Isolation Controller

The ICS-SR2/BR2 series motor intelligent controller is developed for dual-motor electric three-position/two-position switches. Its optimized control program simplifies secondary wiring and delivers precise intelligent control. It supports position signal detection and relay output, accepts passive contact signals to control electric switching, and provides fault protection for drive motors.

Main Function Features

Simplified secondary wiring Intelligent and precise control Motor fault protection

Ratings & Specifications

  • Operating VoltageAC/DC220V,AC/DC110V (AC and DC universal)
  • Ambient temperature-25ºC~+70ºC
  • Altitude≤2500m
  • Power frequency withstand voltageAC2000V/1min

Overall dimension (unit: mm)

Overall dimension (unit: mm)

A digital way out to a green future.

The intelligent energy management system helps users improve management efficiency and achieve the energy-saving and emission reduction target.

MORE
Download documents
Authorization code
If you don't have an authorization code, please send an email via contact.center@pormatrix.us for help.
Confirm
Client manager
Please select your client manager
陈育鑫 Ezzat 臧文明 刘福财 James Zhu 闫涛 谈宏波 陈跃欣 张正辰 王晓杰 雒园 王博博
Your name
E-mail
Company name
Working position
Confirm
Contact Us
Access denied. Please contact your sales engineer.
Note
The video is not available yet.